Goshen Care Center

Fire Safety

Fire Deficiencies
This Nursing home: 2
WY State Average: 6
U.S. Average: 4
WY Deficiencies Range 1–11
Updated April 18, 2013.

How well this home met National Fire Protection Agency standards in the most recent inspection.

January 23, 2013 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Automatic sprinkler systems that have been maintained in working order.
Low
Some
2/5/2013
Exits that are accessible at all times.
Low
Few
2/1/2013

July 24, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Portable fire extinguishers.
Low
Few
8/31/2012
Properly installed electrical wiring and equipment.
Low
Few
7/27/2012
Restrictions on the use of portable space heaters.
Low
Few
7/27/2012

December 20, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
An approved installation, maintenance and testing program for fire alarm systems.
Low
Many
1/5/2012
Automatic sprinkler systems that have been maintained in working order.
Low
Many
2/5/2012
Smoke barrier doors that can resist smoke for at least 20 minutes.
Low
Some
12/21/2011
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
12/21/2011
Walls that prevent smoke from passing through and would resist fire for at least one hour.
Low
Some
2/5/2012
Restrictions on the use of highly flammable decorations.
Low
Some
12/21/2011
Exits that are accessible at all times.
Low
Some
1/5/2012
Heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Low
Some
1/6/2012
Properly installed electrical wiring and equipment.
Low
Some
1/12/2012
Proper medical gas storage and administration areas.
Low
Some
2/5/2012
Record of quarterly fire drills for each shift under varying conditions.
Low
Some
2/5/2012
An approved automatic sprinkler system connected to the fire alarm system.
Low
Some
2/5/2012
Corridor and hallway doors that block smoke.
Low
Few
1/9/2012

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.

Last updated April 18, 2013.


Search Nursing Homes
Advertisement
Nearby Nursing Homes