Onalaska Care Center
Fire Safety
| Fire Deficiencies |
|---|
| This Nursing home: 1 |
| WI State Average: 5 |
| U.S. Average: 4 |
| WI Deficiencies Range 1–19 | Updated April 18, 2013. |
How well this home met National Fire Protection Agency standards in the most recent inspection.
August 08, 2012 Fire Inspection
| Nursing Home Did Not Have: | Possible or Actual Harm | Residents Affected | Date Fixed |
|---|---|---|---|
| Walls that prevent smoke from passing through and would resist fire for at least one hour. | 9/9/2012 |
April 20, 2010 Fire Inspection
| Nursing Home Did Not Have: | Possible or Actual Harm | Residents Affected | Date Fixed |
|---|---|---|---|
| Weekly inspections and monthly testing of generators. | 5/20/2010 | ||
| Heating and ventilation systems that have been properly installed according to the manufacturer's instructions. | 5/20/2010 | ||
| Record of quarterly fire drills for each shift under varying conditions. | 5/20/2010 | ||
| Automatic sprinkler systems that have been maintained in working order. | 5/18/2010 | ||
| Corridor and hallway doors that block smoke. | 5/20/2010 | ||
| Emergency lighting that can last at least 1 1/2 hours. | 5/20/2010 | ||
| An approved installation, maintenance and testing program for fire alarm systems. | 5/20/2010 | ||
| A written emergency evacuation plan. | 5/20/2010 | ||
| Posted "no-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. | 5/20/2010 | ||
| An approved back-up procedure for a faulty fire alarm system. | 5/20/2010 | ||
| Back-up procedures in place for a faulty automatic sprinkler system. | 5/20/2010 |
Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.
Last updated April 18, 2013.