Colonial Manor

Fire Safety

Fire Deficiencies
This Nursing home: 1
TX State Average: 4
U.S. Average: 4
TX Deficiencies Range 1–16
Updated June 19, 2014.

How well this home met National Fire Protection Agency standards in the most recent inspection.

November 14, 2013 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Many
11/14/2013

November 27, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Exits that are accessible at all times.
Low
Many
12/31/2012
Walls that prevent smoke from passing through and would resist fire for at least one hour.
Low
Many
12/28/2012
Heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Very Low
Many
Not Corrected
Weekly inspections and monthly testing of generators.
Very Low
Many
12/19/2012

December 05, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Very Low
Many
Not Corrected

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.

Last updated June 19, 2014.


Search Nursing Homes

Nearby Nursing Homes