Liberty West Nursing Center of Toledo, Inc.

Fire Safety

Fire Deficiencies
This Nursing home: 9
OH State Average: 4
U.S. Average: 4
OH Deficiencies Range 1–28
Updated April 12, 2014.

How well this home met National Fire Protection Agency standards in the most recent inspection.

January 11, 2013 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
An approved installation, maintenance and testing program for fire alarm systems.
Low
Many
2/11/2013
An approved automatic sprinkler system connected to the fire alarm system.
Low
Some
2/11/2013
Approved construction type or materials.
Low
Some
2/11/2013
Automatic sprinkler systems that have been maintained in working order.
Low
Some
2/11/2013
Corridor and hallway doors that block smoke.
Low
Some
2/11/2013
No-smoking signs where oxygen is used.
Low
Some
2/11/2013
Posted "no-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
Low
Some
2/11/2013
Walls that prevent smoke from passing through and would resist fire for at least one hour.
Low
Some
2/11/2013
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
2/11/2013

September 14, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Properly maintained smoke detectors.
Low
Many
10/15/2011
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
10/15/2011
A separate and independent backup electrical power source.
Low
Some
10/15/2011
Automatic sprinkler systems that have been maintained in working order.
Low
Some
10/15/2011
Corridor and hallway doors that block smoke.
Low
Some
10/15/2011
Emergency lighting that can last at least 1 1/2 hours.
Low
Some
10/15/2011
Posted "no-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
Low
Some
10/15/2011
Properly located and lighted "exit" signs.
Low
Some
10/15/2011
Smoke barrier doors that can resist smoke for at least 20 minutes.
Low
Some
10/15/2011

November 03, 2010 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Emergency lighting that can last at least 1 1/2 hours.
Low
Many
12/29/2010
Proper backup exit lighting.
Low
Many
12/29/2010

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.

Last updated April 12, 2014.