Huntington Park Care Center

Fire Safety

Fire Deficiencies
This Nursing home: 6
NE State Average: 5
U.S. Average: 4
NE Deficiencies Range 1–18
Updated April 18, 2013.

How well this home met National Fire Protection Agency standards in the most recent inspection.

December 03, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Emergency lighting that can last at least 1 1/2 hours.
Low
Many
1/17/2013
Record of quarterly fire drills for each shift under varying conditions.
Low
Many
1/17/2013
Other fire safety features required by fire safety codes.
Low
Many
1/17/2013
Fire resistant room wall surfaces.
Low
Many
1/17/2013
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
1/17/2013
Proper medical gas storage and administration areas.
Low
Some
1/17/2013

June 30, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
A separate and independent backup electrical power source.
Low
Many
8/14/2011
Weekly inspections and monthly testing of generators.
Low
Many
6/30/2011
Restrictions on the use of highly flammable decorations.
Low
Many
8/5/2011
Corridor and hallway doors that block smoke.
Low
Many
7/6/2011
Back-up procedures in place for a faulty automatic sprinkler system.
Low
Many
6/30/2011
An approved back-up procedure for a faulty fire alarm system.
Low
Many
6/30/2011
Automatic sprinkler systems that have been maintained in working order.
Low
Some
8/14/2011
Exits that are accessible at all times.
Low
Some
6/30/2011
No-smoking signs where oxygen is used.
Low
Some
7/1/2011
Restrictions on the use of flammable curtains.
Low
Some
8/14/2011
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
8/14/2011

March 31, 2010 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Weekly inspections and monthly testing of generators.
Low
Many
5/9/2010
No-smoking signs where oxygen is used.
Low
Many
5/9/2010
Proper medical gas storage and administration areas.
Low
Many
5/9/2010
Automatic sprinkler systems that have been maintained in working order.
Low
Many
3/31/2010
Properly installed electrical wiring and equipment.
Low
Some
5/9/2010
Proper backup exit lighting.
Low
Some
5/9/2010
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
5/9/2010
An approved automatic sprinkler system connected to the fire alarm system.
Low
Some
3/31/2010
Restrictions on the use of portable space heaters.
Low
Some
4/13/2010
Rooms that can be unlocked from inside without a key.
Low
Some
5/9/2010
Exits that are accessible at all times.
Low
Some
4/13/2010
Corridor and hallway doors that block smoke.
Low
Some
5/9/2010
Properly located and lighted "exit" signs.
Low
Some
5/9/2010