| Fire Deficiencies |
|
This Nursing home:
12
|
|
MT
State Average:
6
|
|
U.S. Average:
4
|
|
MT
Deficiencies Range
1–13
|
Updated April 18, 2013. |
How well this home met National Fire Protection Agency standards in the most recent inspection.
June 07, 2012 Fire Inspection
| Nursing Home Did Not Have: |
Possible or Actual Harm |
Residents Affected |
Date Fixed |
| A two-hour-resistant firewall separation. |
Low
|
Some
|
6/29/2012 |
| Smoke barrier doors that can resist smoke for at least 20 minutes. |
Low
|
Some
|
6/29/2012 |
| Properly installed electrical wiring and equipment. |
Low
|
Some
|
7/19/2012 |
| Portable fire extinguishers. |
Low
|
Some
|
6/29/2012 |
| Exits that are free from obstructions and can be used at all times. |
Low
|
Some
|
7/19/2012 |
| Proper medical gas storage and administration areas. |
Low
|
Few
|
7/19/2012 |
| An approved automatic sprinkler system connected to the fire alarm system. |
Low
|
Few
|
7/19/2012 |
| Corridors that are separated from use areas by walls constructed to limit the passage of smoke. |
Low
|
Few
|
6/29/2012 |
| Weekly inspections and monthly testing of generators. |
Very Low
|
Many
|
6/29/2012 |
| A fire alarm system that can be heard throughout the facility. |
Very Low
|
Many
|
6/29/2012 |
| An approved back-up procedure for a faulty fire alarm system. |
Very Low
|
Many
|
6/29/2012 |
| Back-up procedures in place for a faulty automatic sprinkler system. |
Very Low
|
Many
|
6/29/2012 |
May 25, 2011 Fire Inspection
| Nursing Home Did Not Have: |
Possible or Actual Harm |
Residents Affected |
Date Fixed |
| Corridor and hallway doors that block smoke. |
Low
|
Some
|
6/27/2011 |
| A two-hour-resistant firewall separation. |
Low
|
Some
|
6/27/2011 |
| Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system. |
Low
|
Few
|
6/27/2011 |
| Properly installed electrical wiring and equipment. |
Low
|
Few
|
6/27/2011 |
June 08, 2010 Fire Inspection
| Nursing Home Did Not Have: |
Possible or Actual Harm |
Residents Affected |
Date Fixed |
| Corridor and hallway doors that block smoke. |
Low
|
Many
|
7/23/2010 |
| Properly installed electrical wiring and equipment. |
Low
|
Some
|
7/23/2010 |
| Approved construction type or materials. |
Low
|
Some
|
7/23/2010 |
| Proper backup exit lighting. |
Low
|
Few
|
7/23/2010 |
| Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system. |
Low
|
Few
|
7/23/2010 |
| Fire resistant room wall surfaces. |
Low
|
Few
|
7/23/2010 |
Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.
Last updated
April 18, 2013.