Festus Manor

Fire Safety

Fire Deficiencies
This Nursing home: 3
MO State Average: 3
U.S. Average: 4
MO Deficiencies Range 1–13
Updated April 12, 2014.

How well this home met National Fire Protection Agency standards in the most recent inspection.

July 24, 2013 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Properly installed electrical wiring and equipment.
Low
Some
9/1/2013
Exits that are accessible at all times.
Low
Some
9/1/2013
Emergency lighting that can last at least 1 1/2 hours.
Low
Some
9/1/2013

July 13, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Automatic sprinkler systems that have been maintained in working order.
Low
Many
8/27/2012
Properly installed electrical wiring and equipment.
Low
Many
8/27/2012
Approved construction type or materials.
Low
Some
8/27/2012
An approved automatic sprinkler system connected to the fire alarm system.
Low
Some
8/27/2012
Properly installed hallway dispensers for alcohol-based hand rub.
Low
Some
8/27/2012

August 17, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Weekly inspections and monthly testing of generators.
Low
Many
9/30/2011
Posted "no-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
Low
Many
9/30/2011
Record of quarterly fire drills for each shift under varying conditions.
Low
Some
9/30/2011
Exits that are accessible at all times.
Low
Some
9/30/2011
Portable fire extinguishers.
Low
Some
9/30/2011
An approved installation, maintenance and testing program for fire alarm systems.
Low
Some
9/30/2011

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.