Our Lady of Angels Retirement Home

Fire Safety

Fire Deficiencies
This Nursing home: 7
IL State Average: 7
U.S. Average: 4
IL Deficiencies Range 1–29
Updated April 18, 2013.

How well this home met National Fire Protection Agency standards in the most recent inspection.

May 01, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
A two-hour-resistant firewall separation.
Low
Many
5/10/2012
Weekly inspections and monthly testing of generators.
Low
Many
5/10/2012
Heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Low
Many
5/10/2012
A written emergency evacuation plan.
Low
Many
5/11/2012
Automatic sprinkler systems that have been maintained in working order.
Low
Many
5/11/2012
Walls that prevent smoke from passing through and would resist fire for at least one hour.
Low
Some
5/10/2012
Smoke barrier doors that can resist smoke for at least 20 minutes.
Low
Some
5/4/2012

March 09, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
A two-hour-resistant firewall separation.
Low
Many
4/4/2011
Automatic sprinkler systems that have been maintained in working order.
Low
Some
4/4/2011
Corridor and hallway doors that block smoke.
Low
Some
4/4/2011
Proper medical gas storage and administration areas.
Low
Some
4/4/2011
Proper stairway enclosures and vertical shafts.
Low
Some
4/4/2011
Properly installed electrical wiring and equipment.
Low
Few
4/4/2011

June 03, 2010 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
A two-hour-resistant firewall separation.
Low
Many
6/23/2010
Approved construction type or materials.
Low
Many
6/23/2010
An automatic smoke detection system in all hallways.
Low
Many
6/23/2010
Proper stairway enclosures and vertical shafts.
Low
Many
6/23/2010
Properly maintained smoke detectors.
Low
Many
6/23/2010
Record of quarterly fire drills for each shift under varying conditions.
Low
Many
6/23/2010
An approved installation, maintenance and testing program for fire alarm systems.
Low
Many
6/23/2010
A written emergency evacuation plan.
Low
Many
6/23/2010
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Many
6/23/2010
Weekly inspections and monthly testing of generators.
Low
Many
6/23/2010
Corridor and hallway doors that block smoke.
Low
Some
6/23/2010

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.

Last updated April 18, 2013.


Search Nursing Homes
Advertisement
Nearby Nursing Homes