Fireside House of Centralia

Fire Safety

Fire Deficiencies
This Nursing home: 9
IL State Average: 7
U.S. Average: 4
IL Deficiencies Range 1–23
Updated June 19, 2014.

How well this home met National Fire Protection Agency standards in the most recent inspection.

December 23, 2013 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
An approved installation, maintenance and testing program for fire alarm systems.
Low
Many
1/15/2014
Weekly inspections and monthly testing of generators.
Low
Many
1/15/2014
Properly protected cooking facilities.
Low
Some
1/15/2014
Portable fire extinguishers.
Low
Some
1/15/2014
No-smoking signs where oxygen is used.
Low
Some
1/15/2014
Emergency lighting that can last at least 1 1/2 hours.
Low
Some
1/15/2014
Corridor and hallway doors that block smoke.
Low
Some
1/15/2014
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
1/15/2014
Properly installed electrical wiring and equipment.
Low
Few
1/15/2014

December 05, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Exits that are accessible at all times.
Low
Some
12/27/2012
Corridor and hallway doors that block smoke.
Low
Some
12/27/2012
Proper backup exit lighting.
Low
Some
12/27/2012
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
12/27/2012
Walls that prevent smoke from passing through and would resist fire for at least one hour.
Low
Some
12/27/2012
Automatic sprinkler systems that have been maintained in working order.
Low
Few
12/27/2012

January 30, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Automatic sprinkler systems that have been maintained in working order.
Low
Many
3/17/2012
An approved installation, maintenance and testing program for fire alarm systems.
Low
Many
3/24/2012
An approved back-up procedure for a faulty fire alarm system.
Low
Many
2/10/2012
Properly maintained smoke detectors.
Low
Many
3/24/2012
Weekly inspections and monthly testing of generators.
Low
Many
3/29/2012
Back-up procedures in place for a faulty automatic sprinkler system.
Low
Many
2/10/2012
Posted "no-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
Low
Some
2/17/2012
Corridor and hallway doors that block smoke.
Low
Some
2/6/2012
Properly protected cooking facilities.
Low
Some
2/10/2012
Walls that prevent smoke from passing through and would resist fire for at least one hour.
Low
Some
2/8/2012
Record of quarterly fire drills for each shift under varying conditions.
Very Low
Many
3/17/2012

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.

Last updated June 19, 2014.