| Fire Deficiencies |
|
This Nursing home:
14
|
|
IL
State Average:
7
|
|
U.S. Average:
4
|
|
IL
Deficiencies Range
1–29
|
Updated April 18, 2013. |
How well this home met National Fire Protection Agency standards in the most recent inspection.
August 22, 2012 Fire Inspection
| Nursing Home Did Not Have: |
Possible or Actual Harm |
Residents Affected |
Date Fixed |
| An adequate water supply for the sprinkler system. |
Low
|
Many
|
9/5/2012 |
| Corridor and hallway doors that block smoke. |
Low
|
Some
|
9/7/2012 |
| Smoke barrier doors that can resist smoke for at least 20 minutes. |
Low
|
Some
|
9/11/2012 |
| Proper medical gas storage and administration areas. |
Low
|
Some
|
9/10/2012 |
| Properly maintained smoke detectors. |
Low
|
Some
|
9/17/2012 |
| Properly located and lighted "exit" signs. |
Low
|
Some
|
8/23/2012 |
| Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system. |
Low
|
Some
|
9/11/2012 |
| A two-hour-resistant firewall separation. |
Low
|
Some
|
9/10/2012 |
| Properly installed electrical wiring and equipment. |
Low
|
Few
|
9/21/2012 |
| Posted "no-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed. |
Low
|
Few
|
9/10/2012 |
| A written emergency evacuation plan. |
Very Low
|
Many
|
9/21/2012 |
| An approved back-up procedure for a faulty fire alarm system. |
Very Low
|
Many
|
9/10/2012 |
| Back-up procedures in place for a faulty automatic sprinkler system. |
Very Low
|
Many
|
9/10/2012 |
| Record of quarterly fire drills for each shift under varying conditions. |
Very Low
|
Many
|
9/19/2012 |
June 29, 2011 Fire Inspection
| Nursing Home Did Not Have: |
Possible or Actual Harm |
Residents Affected |
Date Fixed |
| Properly working alarms on sprinkler valves. |
Low
|
Many
|
12/8/2011 |
| Proper construction of ducts through walls designed to prevent smoke passage. |
Low
|
Many
|
8/15/2011 |
| Corridors that are separated from use areas by walls constructed to limit the passage of smoke. |
Low
|
Many
|
8/15/2011 |
| Automatic sprinkler systems that have been maintained in working order. |
Low
|
Many
|
7/29/2011 |
August 12, 2010 Fire Inspection
| Nursing Home Did Not Have: |
Possible or Actual Harm |
Residents Affected |
Date Fixed |
| Record of quarterly fire drills for each shift under varying conditions. |
Low
|
Many
|
8/26/2010 |
| Properly located and lighted "exit" signs. |
Low
|
Some
|
8/13/2010 |
| Properly protected cooking facilities. |
Low
|
Some
|
8/13/2010 |
| Properly installed electrical wiring and equipment. |
Low
|
Some
|
8/24/2010 |
Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.