Apostolic Christian Home of Eureka

Fire Safety

Fire Deficiencies
This Nursing home: 7
IL State Average: 7
U.S. Average: 4
IL Deficiencies Range 1–23
Updated April 12, 2014.

How well this home met National Fire Protection Agency standards in the most recent inspection.

November 08, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Exit stairways and towers that are smoke proof.
Low
Many
12/28/2012
Walls that prevent smoke from passing through and would resist fire for at least one hour.
Low
Some
12/28/2012
Heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Low
Some
11/9/2012
Properly installed electrical wiring and equipment.
Low
Some
11/8/2012
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
11/21/2012
Approved construction type or materials.
Low
Some
12/18/2012
Corridor and hallway doors that block smoke.
Low
Some
11/8/2012

November 28, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Record of quarterly fire drills for each shift under varying conditions.
Low
Many
12/19/2011
Properly maintained smoke detectors.
Low
Many
12/23/2011
Properly protected cooking facilities.
Low
Some
12/20/2011

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.

Last updated April 12, 2014.


Search Nursing Homes

Nearby Nursing Homes