Anna Rehabilitation & Nursing Center

Fire Safety

Fire Deficiencies
This Nursing home: 5
IL State Average: 7
U.S. Average: 4
IL Deficiencies Range 1–29
Updated April 18, 2013.

How well this home met National Fire Protection Agency standards in the most recent inspection.

October 02, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
An automatic smoke detection system in all hallways.
Low
Many
10/25/2012
Weekly inspections and monthly testing of generators.
Low
Many
10/25/2012
Approved construction type or materials.
Low
Some
11/14/2012
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
10/25/2012
Corridor and hallway doors that block smoke.
Low
Some
10/25/2012

November 01, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Corridor and hallway doors that block smoke.
Low
Many
11/28/2011
Approved construction type or materials.
Low
Many
11/28/2011
Properly maintained smoke detectors.
Low
Many
11/29/2011
Posted "no-smoking" signs in areas where smoking is not permitted or ashtrays provided where smoking was allowed.
Low
Some
11/29/2011
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Some
11/29/2011
Properly installed electrical wiring and equipment.
Low
Some
11/29/2011
Proper backup exit lighting.
Low
Some
11/2/2011
Automatic sprinkler systems that have been maintained in working order.
Low
Few
11/29/2011

December 15, 2010 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Weekly inspections and monthly testing of generators.
Low
Many
1/14/2011
Properly maintained smoke detectors.
Low
Many
1/13/2011
Properly installed electrical wiring and equipment.
Low
Some
1/11/2011
Smoke barrier doors that can resist smoke for at least 20 minutes.
Low
Some
1/11/2011
Exits that are accessible at all times.
Low
Few
1/11/2011
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Few
1/11/2011
Properly protected cooking facilities.
Low
Few
1/11/2011
Corridor and hallway doors that block smoke.
Low
Few
1/11/2011
No-smoking signs where oxygen is used.
Low
Few
1/11/2011
Record of quarterly fire drills for each shift under varying conditions.
Very Low
Many
1/11/2011

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.

Last updated April 18, 2013.