Subacute/Saratoga

Fire Safety

Fire Deficiencies
This Nursing home: 7
CA State Average: 5
U.S. Average: 4
CA Deficiencies Range 1–20
Updated April 12, 2014.

How well this home met National Fire Protection Agency standards in the most recent inspection.

March 11, 2013 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Properly working alarms on sprinkler valves.
Low
Many
4/29/2013
Portable fire extinguishers.
Low
Some
4/29/2013
An approved installation, maintenance and testing program for fire alarm systems.
Low
Some
6/10/2013
Emergency lighting that can last at least 1 1/2 hours.
Low
Some
4/29/2013
Automatic sprinkler systems that have been maintained in working order.
Low
Few
4/29/2013
Record of quarterly fire drills for each shift under varying conditions.
Low
Few
4/29/2013
Corridor and hallway doors that block smoke.
Low
Few
4/29/2013

April 19, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Approved construction type or materials.
Low
Some
6/22/2012
Corridor and hallway doors that block smoke.
Low
Some
6/22/2012
Exits that are free from obstructions and can be used at all times.
Low
Few
6/22/2012
An approved automatic sprinkler system connected to the fire alarm system.
Low
Few
6/22/2012
Automatic sprinkler systems that have been maintained in working order.
Low
Few
6/22/2012

April 06, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Weekly inspections and monthly testing of generators.
Low
Many
5/25/2011
Properly working alarms on sprinkler valves.
Low
Many
5/25/2011
Proper medical gas storage and administration areas.
Low
Some
5/25/2011
An approved installation, maintenance and testing program for fire alarm systems.
Low
Some
5/25/2011
Properly installed hallway dispensers for alcohol-based hand rub.
Low
Few
5/25/2011
Exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Low
Few
5/25/2011
Corridors that are separated from use areas by walls constructed to limit the passage of smoke.
Low
Few
5/25/2011
Automatic sprinkler systems that have been maintained in working order.
Low
Few
5/25/2011
Approved construction type or materials.
Low
Few
5/25/2011

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.