Bethany Home Society San Joaquin CO

Fire Safety

Fire Deficiencies
This Nursing home: 7
CA State Average: 5
U.S. Average: 4
CA Deficiencies Range 1–20
Updated April 12, 2014.

How well this home met National Fire Protection Agency standards in the most recent inspection.

March 21, 2013 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Restrictions on the use of flammable curtains.
Low
Few
4/9/2013
Proper medical gas storage and administration areas.
Low
Few
4/9/2013
Approved construction type or materials.
Low
Few
4/9/2013
Smoke barrier doors that can resist smoke for at least 20 minutes.
Low
Few
4/9/2013
Properly installed electrical wiring and equipment.
Low
Few
4/9/2013
Portable fire extinguishers.
Low
Few
4/9/2013
Automatic sprinkler systems that have been maintained in working order.
Low
Few
4/9/2013

June 14, 2012 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Weekly inspections and monthly testing of generators.
Low
Some
7/30/2012
Walls that prevent smoke from passing through and would resist fire for at least one hour.
Low
Some
7/30/2012
Exit doors that are held open by devices that will automatically close on the activation of a fire alarm or smoke detector.
Low
Few
7/30/2012
Approved construction type or materials.
Low
Few
7/30/2012
Automatic sprinkler systems that have been maintained in working order.
Low
Few
7/30/2012
A written emergency evacuation plan.
Low
Few
7/30/2012
Special areas constructed so that walls can resist fire for one hour or an approved fire extinguishing system.
Low
Few
7/30/2012

March 08, 2011 Fire Inspection

Nursing Home Did Not Have: Possible or Actual Harm Residents Affected Date Fixed
Approved construction type or materials.
Low
Few
4/1/2011
Record of quarterly fire drills for each shift under varying conditions.
Low
Few
4/1/2011
Proper medical gas storage and administration areas.
Low
Few
4/1/2011
Properly located and lighted "exit" signs.
Low
Few
4/1/2011
Properly installed electrical wiring and equipment.
Low
Few
4/1/2011
Heating and ventilation systems that have been properly installed according to the manufacturer's instructions.
Low
Few
4/1/2011
Emergency lighting that can last at least 1 1/2 hours.
Low
Few
4/1/2011
Automatic sprinkler systems that have been maintained in working order.
Low
Few
4/1/2011

Note: Because of differences in calculation, all data may not match those shown on Nursing Home Compare, a website run by the federal Centers for Medicare & Medicaid Services. CMS has approved the U.S. News methodology.

Last updated April 12, 2014.


Search Nursing Homes

Nearby Nursing Homes